Rockwell Automation 1769-SM2 Compact I/O DSI/Modbus Communication Module User Manual
Page 46

3-8
Configuring the Module
See
for descriptions of these configuration words.
5. Click OK when finished. The MicroLogix 1500 will download the
configuration data to the 1769-SM2 module when the controller is
placed in run mode.
Special Case— Data Entry for 2 Stop Bits Communication
The Chan.1, Chan. 2, and Chan 3 tabs do not allow settings that specify 2
stop bits communication in Modbus RTU operation. For this type of
configuration, you must use the Generic Extra Data Config tab to enter
the data by performing these steps:
1. To configure a specific 1769-SM2 module channel for 2 stop bits
communication, click on the Generic Extra Data Config tab.
2. On the Generic Extra Data Config tab screen, enter the appropriate
in the offset addresses highlighted in
.
Figure 3.6 Entering Data for 2 Stop Bits on Generic Extra Data Config Screen
Table 3.D Entry Data for 2 Stop Bits Communication
1769-SM2 CH
Offset Address
Value
Description
1
10
3
4
5
Sets CH1 for 8-N-2 format
Sets CH1 for 8-E-2 format
Sets CH1 for 8-O-2 format
2
24
3
4
5
Sets CH2 for 8-N-2 format
Sets CH2 for 8-E-2 format
Sets CH2 for 8-O-2 format
3
38
3
4
5
Sets CH3 for 8-N-2 format
Sets CH3 for 8-E-2 format
Sets CH3 for 8-O-2 format