Chapter 2, Installing the module, Preparing for an installation – Rockwell Automation 1769-SM2 Compact I/O DSI/Modbus Communication Module User Manual
Page 23: Preparing for an installation -1, 2installing the module

Chapter
2
Installing the Module
This chapter provides instructions for installing the 1769-SM2 as an
expansion I/O module on MicroLogix 1500 and CompactLogix
controllers, or with a remote 1769-based adapter.
Consider the following when installing the 1769-SM2 module:
•
Verify that you have all required equipment. Refer to
•
A MicroLogix 1500 Base Unit or Compact I/O power supply has
limits in the amount of +5V dc and +24V dc current it can supply to
modules in its I/O bank. These limits depend on the catalog number
(e.g. 1769-PA2) of the power supply. A bank of modules must not
exceed the current limits of the MicroLogix 1500 Base Unit or I/O
bank power supply.
Refer to the MicroLogix 1500 User Manual (publication
1764-UM001
)
or the Compact 1769 Expansion I/O Power Supplies
Installation Instructions (publication 1769-5.14).
•
The module has a distance rating of four. Therefore, the module must
be within four modules of the I/O bank’s power supply.
Topic
Page
Setting the Configuration Mode Switch
Setting the Operating Mode Switch (Single/Multi-Drive)
Assembling the Module to the Controller
Replacing the Module within a System
Connecting Drive(s) to the Module
Viewing Start-Up Status Indicators
Preparing for an Installation