Dsi diagnostic object, Class code, Services – Rockwell Automation 1769-SM2 Compact I/O DSI/Modbus Communication Module User Manual
Page 186: Instances, Class attributes, C-16

C-16
CIP/DSI Objects
Class Code
Services
Instances
The number of instances depends on the maximum number of diagnostic
items in the device. The total number of diagnostic items can be read in
Instance 0, Attribute 2.
Class Attributes
DSI Diagnostic Object
Hexadecimal
Decimal
0x99
153
Service Code
Implemented for:
Service Name
Class
Instance
0x0E
Yes
Yes
Get_Attribute_Single
0x10
Yes
Yes
Set_Attribute_Single
Instances (Dec.)
Single-Drive Mode
Multi-Drive Mode
0…16383
Instances 0…16383 in drive
Instances 0…16383 in Drive 0
16384…17407
Instances 0…1023 in module
Instances 0…1023 in module
17408…18431
Instances 0…1023 in module
Instances 0…1023 in Drive 1
18432…19455
Instances 0…1023 in slave
Instances 0…1023 in Drive 2
19456…20479
Not supported
Instances 0…1023 in Drive 3
20480…21503
Not supported
Instances 0…1023 in Drive 4
21504…22527
Not supported
Instances 0…1023 in module
Attribute
ID
Access
Rule
Name
Data Type
Description
1
Get
Class Revision
WORD
1
2
Get
Number of
Instances
WORD
Number of diagnostic items in the
device
3
Get
ENUM Offset
WORD
DSI ENUM object instance offset