Setting the configuration mode switch, Setting the configuration mode switch -3 – Rockwell Automation 1769-SM2 Compact I/O DSI/Modbus Communication Module User Manual
Page 25

Installing the Module
2-3
Before installing the module, make sure its Configuration Mode Switch
is correctly set. See
Configuration Methods on page 3-3
for details on
the Controller and Parameter configuration modes. Then set the
Configuration Mode Switch (SW1 in
) for your application.
Figure 2.1 Configuration Mode and Single/Multi-Drive Operation Switch Locations
Setting the Configuration Mode Switch
SW1 Setting
Description
CONT (Controller)
back position
Default setting—The 1769-SM2 module uses the configuration
data downloaded from the controller on power-up and when the
controller is placed in run mode.
PARAM (Parameter)
front position
The 1769-SM2 module uses its internal parameter settings to
configure the module.
(Controller
Position)
(Single
Position)
(Parameter
Position)
(Multi-Drive
Position)
Configuration
Mode Switch
(SW1)
Operating
Mode Switch
(SW2)
CONT
PARAM
1X
5X