Multi-drive mode – Rockwell Automation 1769-SM2 Compact I/O DSI/Modbus Communication Module User Manual
Page 33

Installing the Module
2-11
When connecting a drive to the channel port using 22-RJ45CBL-C20
communications cable, the above drive parameters do not require
configuration because the drive senses that a DSI peripheral is connected
and it ignores these parameter settings.
Multi-Drive Mode
For Multi-Drive mode, each channel port MUST be connected to the
drives via daisy-chaining using AK-U0-RJ45-TB2P terminal block
connectors (one for the port connection and one for each drive
connection) and twisted pair network wiring (Belden No. 3105A or
equivalent). The 22-RJ45CBL-C20 communications cable and splitter
cables cannot be used.
Important: The following drive parameters MUST be configured to the
settings shown so that the 1769-SM2 module will
communicate with the drives:
Changes to these drive parameters require the drive to be
reset for the new settings to take effect.
Drive Parameter
Setting
A103 - [Comm Data Rate]
“4” (19.2K)
A104 - [Comm Node Addr]
Value of Drive Addr x parameter in the
1769-SM2
A107 - [Comm Format]
“0” (RTU 8-N-1)