Overview Chapter 1

System Overview

The module communicates to the controller through the bus interface.
The module also receives 5 and 24V DC power through the bus
interface.

You can install as many analog modules as your power supply can
support. However, the modules may not be located more than eight
modules away from the system power supply.

Determine Power Supply Distance

Module Operation

When you cycle power, the module performs a check of its internal
circuits, memory, and basic functions. During this time, the
module-status OK indicator remains off. If no faults are found during
power-cycle diagnostics, the module-status OK indicator is turned on.

After power-cycle checks are complete, the module waits for valid
channel-configuration data. If an invalid configuration is detected, the
module generates a configuration error. Once a channel is properly
configured and enabled, the module begins its conversion process.

Each time a new output value is sent to the module, it is tested against
user-configured high and low output clamps for each output channel.
If output values equal to or exceeding either of these clamp levels are
detected, the value sent to the module is clamped at that limit by the
module, and unique bits are set in the output-channel status word.

1

1

1

2

3

4

3

2

2

3

4

System Power Supply

Compact I/O

Compact I/O

Compact I/O

En

d Ca

p

CompactLogix

Controller

or I/O

Commu

nicat

io

n

Ad

ap

te

r

Compact I/O

Compact I/O

Co

m

pa

ct

I/

O

or

Power Supply Distance

Compact I/O

Compact I/

O

Compact I/O

Compact I/O

En

d Ca

p

MicroLogix 1500 Controller

with Integrated System

Power Supply

Power Supply Distance