Module Data, Status, and Channel Configuration Chapter 3
This table describes how the ramp rate is determined for all output
types/ranges and output data formats.
If configured, ramping takes place only when the output is
commanded to go to a fault state. Ramping does not occur during
normal run operation.
Ramp Rates for Output Type/Range and Data Formats
Output Data Format
Output Type/Range
Total Counts in Full Scale Number of Counts for
Every 1% of Ramp Rate
Real Units/Second for
Every 1% of Ramp Rate
Proportional Counts
-10…10V DC
65,534
(1)
655
0.21V/s
0…5V DC
0.058V/s
0…10V DC
0.11V/s
1…5V DC
0.048V/s
0…20 mA
0.21 mA/s
4…20 mA
0.178 mA/s
Engineering Units
-10…10V DC
21,000
210
0.21V/s
0…5V DC
5750
58
0.058V/s
0…10V DC
11,000
110
0.11V/s
1…5V DC
4750
48
0.048V/s
0…20 mA
21,000
210
0.21 mA/s
4…20 mA
17,800
178
0.178 mA/s
Scaled for PID
-10…10V DC
17,203
172
0.21V/s
0…5V DC
18,840
188
0.058V/s
0…10V DC
18,021
180
0.11V/s
1…5V DC
19,455
195
0.048V/s
0…20 mA
17,202
172
0.21 mA/s
4…20 mA
18,226
182
0.178 mA
Percent of Full Scale
-10…10V DC
21,000
210
0.21V/s
0…5V DC
11,500
115
0.058V/s
0…10V DC
11,000
110
0.11V/s
1…5V DC
11,875
119
0.048V/s
0…20 mA
10,500
105
0.21 mA/s
4…20 mA
11,125
111
0.178 mA/s
(1) Limited to 32,767 by programming software.