Publication 1769-UM020A-EN-P - December 2009

39

Module Data, Status, and Channel Configuration Chapter 3

This table describes how the ramp rate is determined for all output
types/ranges and output data formats.

If configured, ramping takes place only when the output is
commanded to go to a fault state. Ramping does not occur during
normal run operation.

Ramp Rates for Output Type/Range and Data Formats

Output Data Format

Output Type/Range

Total Counts in Full Scale Number of Counts for

Every 1% of Ramp Rate

Real Units/Second for
Every 1% of Ramp Rate

Proportional Counts

-10…10V DC

65,534

(1)

655

0.21V/s

0…5V DC

0.058V/s

0…10V DC

0.11V/s

1…5V DC

0.048V/s

0…20 mA

0.21 mA/s

4…20 mA

0.178 mA/s

Engineering Units

-10…10V DC

21,000

210

0.21V/s

0…5V DC

5750

58

0.058V/s

0…10V DC

11,000

110

0.11V/s

1…5V DC

4750

48

0.048V/s

0…20 mA

21,000

210

0.21 mA/s

4…20 mA

17,800

178

0.178 mA/s

Scaled for PID

-10…10V DC

17,203

172

0.21V/s

0…5V DC

18,840

188

0.058V/s

0…10V DC

18,021

180

0.11V/s

1…5V DC

19,455

195

0.048V/s

0…20 mA

17,202

172

0.21 mA/s

4…20 mA

18,226

182

0.178 mA

Percent of Full Scale

-10…10V DC

21,000

210

0.21V/s

0…5V DC

11,500

115

0.058V/s

0…10V DC

11,000

110

0.11V/s

1…5V DC

11,875

119

0.048V/s

0…20 mA

10,500

105

0.21 mA/s

4…20 mA

11,125

111

0.178 mA/s

(1) Limited to 32,767 by programming software.