47

Module Diagnostics and Troubleshooting Chapter 4

Error Codes

Error codes can help troubleshoot your module.

During system configuration, if you set the fields in the configuration
file to invalid or unsupported values, the module generates a
configuration error and the system controller enters a Fault condition.
The invalid configuration data must be corrected and the program
downloaded again for the system to enter Run mode. You cannot
change module configuration data while the system is in Run mode.
Any changes are ignored by the module, which continues to operate
with its previous configuration.

Extended Error Codes for Hardware Errors

Error Type

Hex

Equivalent

(1)

Module

Error

Code

Extended Error

Information

Code

Error Description

Binary

Binary

No Error

X000

000

0 0000 0000

No error

General Common
Hardware Error

X200

001

0 0000 0000

General hardware error; no additional information

X201

001

0 0000 0001

Power-up reset state

Hardware-
specific Error

X300

001

1 0000 0000

General hardware error

X301

001

1 0000 0001

Microprocessor hardware error

X302

001

1 0000 0010

D/A converter communication error

(1) X represents the Don’t Care digit. Module hardware error codes are typically presented in their Hex Equivalent by the programming software.

Extended Error Codes for Configuration Errors

Hex Equivalent

(1)

Module

Error Code

Extended Error

Information Code

Error Description

Binary

Binary

X400

010

0 0000 0000

General configuration error; reserve bits set to 1

X401

010

0 0000 0001

Invalid output range selected (channel 0)

X402

010

0 0000 0010

Invalid output range selected (channel 1)

X403

010

0 0000 0011

Invalid output range selected (channel 2)

X404

010

0 0000 0100

Invalid output range selected (channel 3)

X405

010

0 0000 0101

Invalid output format selected (channel 0)

X406

010

0 0000 0110

Invalid output format selected (channel 1)

X407

010

0 0000 0111

Invalid output format selected (channel 2)

X408

010

0 0000 1000

Invalid output format selected (channel 3)

X409

010

0 0000 1001

Invalid fault value (channel 0)

X40A

010

0 0000 1010

Invalid fault value (channel 1)

X40B

010

0 0000 1011

Invalid fault value (channel 2)

X40C

010

0 0000 1100

Invalid fault value (channel 3)

Advertising