Publication 1769-UM020A-EN-P - December 2009

Appendix C Configuration Using the RSLogix 5000 Generic Profile for CompactLogix Controllers

Configure Each I/O Module

Once you have created Generic Profiles for each analog I/O module
in your system, you must then enter configuration information into the
Tag database that has been automatically created from the Generic
Profile information you entered for each of these modules. This
configuration information is downloaded to each module at program
download, at going to run, and at power cycle.

Tag addresses are automatically created for configured I/O modules.
All local I/O addresses are preceded by the word Local. These
addresses have the following format:

Input Data: Local:

s.I

Output Data: Local:

s.O

Configuration Data: Local:

s.C

Where

s is the slot number assigned the I/O modules in the

Generic Profiles.

1. Open the Controller Tag database by double-clicking Controller

Tags in the upper portion of the controller organizer.

2. Open the configuration tag for your module by clicking on the

plus sign to the left of its configuration tag in the tag database.

3. To configure the input modules in slot 1, click the plus sign left

of Local:1.C.

4. Click the plus sign to the left of Local:1.C.Data to reveal the 32

data words where the configuration data may be entered for the
module.