Module Data, Status, and Channel Configuration Chapter 3

Engineering Units

The value sent by the controller to the output channel is the actual
current or voltage value for the selected output range. The resolution
of the engineering units is 0.001V or 0.001 mA per count.

Scaled-for-PID

The value sent by the controller to the output channel is a signed
integer with 0 representing the lower limit of the normal operating
range and 16,383 representing the upper limit of the normal operating
range. Allen-Bradley controllers, such as the MicroLogix 1500
controller, use this range in their PID equations. The amount over and
under the normal operating range (the full-scale range) is also
supported.

Percent Range

The value sent by the controller to the output channel is presented as
a percentage of the normal operating range selected for that output
channel. For example, 0…10V DC equals 0…100%. The resolution of
the percent range is 0.01% per count. The amount over and under the
normal operating range (the full-scale range) is also supported.

Valid Output Data Word Formats/Ranges

This table shows the valid formats and minimum/maximum data
ranges provided by the module.

Valid Output Data

Normal
Operating
Output Range

Full Range

(1)

Raw/
Proportional
Data

Engineering
Units

(2)

Scaled-for-PID

Percent Range

(3)

Full Range

Full Range

Normal
Operating
Range

Full Range

Normal
Operating
Range

Full Range

-10…10V DC

-10.5…10.5V

-32,767…
32,767

-10,500…10,500

0…16,383

-410…16,793

-10,000…
10,000

-10,500…10,500

0…5V DC

-0.5…5.25V

-500…5,250

-1638…17,202

0…10,000

-1000…10,500

0…10V DC

-0.5…10.5V

-500…10,500

-819…17,202

-500…10,500

1…5V DC

0.5…5.25V

500…5,250

-2048…17,407

-1250…10,625

0…20 mA

0…21 mA

0…21,000

0…17,202

0…10,500

4…20 mA

3.2…21 mA

3,200… 21,000

-819…17,407

-500…10,625

(1) Includes amounts over and under normal operating range.
(2) 1 count = 0.001V or 0.001 mA.
(3) 1 count = 0.01%.