Mount to a panel, Structions, see, Panel mounting by using the – Rockwell Automation 1769-OF4 Compact Analog Output Module User Manual

Page 18

Advertising
background image

18

Publication 1769-UM020A-EN-P - December 2009

Chapter 2 Installation and Wiring

Mount to a Panel

Mount the module to a panel by using two screws per module. Use
M4 or #8 panhead screws. Mounting screws are required on every
module.

Panel Mounting By Using the Dimensional Template

Locate holes every 17.5 mm (0.689 in.) to allow for a mix of
single-wide and one-and-a-half-wide modules (for example, the
1769-OA16 module).

Panel Mounting By Using the Modules as a Template

This procedure lets you use the assembled modules as a template for
drilling holes in the panel. If you have sophisticated panel-mounting
equipment, you can use the dimensional template provided. Due to
module mounting-hole tolerance, it is important to follow these
procedures.

1. On a clean work surface, assemble no more than three modules.

2. Using the assembled modules as a template, carefully mark the

center of all module-mounting holes on the panel.

3. Return the assembled modules to the clean work surface,

including any previously mounted modules.

4. Drill and tap the mounting holes for the recommended M4 or #8

screw.

5. Place the modules back on the panel, and check for proper hole

alignment.

132 mm (5.197 in.)

122.6 mm

(4.826 in.)

Host Cont

roller

Refer to host controller documentation for this dimension.

Spacing for single-wide modules 35 mm (1.378 in.).

Overall hole spacing tolerance:
±0.4 mm (0.016 in.).

Spacing for one-and-a-half-wide modules 52.5 mm (2.067 in.).