Output specifications – 1769-of4 – Rockwell Automation 1769-OF4 Compact Analog Output Module User Manual

Page 52

Advertising
background image

52

Publication 1769-UM020A-EN-P - December 2009

Appendix A Specifications

Output Specifications –
1769-OF4

Vendor I.D. code

1

Product type code

10

Product code

48

Input words

5

Output words

5

Configuration words

32

Attribute

1769-OF4

Attribute

1769-OF4

Analog normal operating
ranges

(1)

(1) The over- or under-range flag will come on when either the High Clamp or the Low Clamp values are exceeded.

When either range flag is set, the module clamps the corresponding channel’s output to the High Clamp or the
Low Clamp value. Unless latched, the flag automatically resets when directed to a value between the High
Clamp and the Low Clamp values. The output channel value always returns to normal operation when directed
to a value allowed by the High Clamp and Low Clamp values (even if latching of the Clamp status bits is
enabled).

0…20 mA, 4…20 mA, ±10V DC, 0…10V DC,
0…5V DC, 1…5V DC

Full scale analog ranges

(1)

0…21 mA, 3.2…21 mA, ±10.5V DC, -0.5…10.5V DC,
-0.5… 5.25V DC, 0.5… 5.25V DC

Number of outputs

4 single-ended, voltage or current

Digital resolution across full
range

15 bits plus sign unipolar and bipolar

Conversion rate (all channels)
max

Interrupts not enabled: 2.5 ms
Interrupts enabled: 3.8 ms

Step response to 63%

(2)

(2) Step response is the period of time between when the D/A converter was instructed to go from minimum to full

range until the device is at 63% of full range.

2.9 ms

Resistive load

Current: 0…600

Ω

(includes wire resistance)

Voltage: 1 k

Ω

or greater

Inductive load, max.

0.1 mH (current loads), 1.0 µF (voltage loads)

Field Calibration

None required

Overall Accuracy

(3)

(3) Includes offset, gain, drift, non-linearity, and repeatability error terms.

0.5% full scale at 25 °C (77 °F)