1 - overview, Introduction, Module description – Rockwell Automation 1769-OF4 Compact Analog Output Module User Manual

Page 9: Chapter 1, Overview, Introduction module description, Chapter

Advertising
background image

9

Publication 1769-UM020A-EN-P - December 2009

9

Chapter

1

Overview

Introduction

Module Description

The module converts digital data from controllers to provide analog
output data. The module provides the following output types and
ranges.

The data can be configured as:

engineering units.

scaled-for-PID.

percent range.

raw/proportional data.

Module configuration is normally done via the controller’s
programming software. In addition, some controllers support
configuration via the user program. In either case, the module
configuration is stored in the memory of the controller. Refer to your
controller’s user manual for more information.

Topic

Page

Module Description

9

System Overview

11

Module Operation

11

Normal and Full Ranges

Signal Type

Normal Operating Input Range

Full Module Range

Voltage

±10V DC

± 10.5V DC

1…5V DC

0.5…5.25V DC

0…5V DC

-0.5…5.25V DC

0…10V DC

-0.5…10.5V DC

Current

0…20 mA

0…21 mA

4…20 mA

3.2…21 mA

Advertising