Chapter 2 Installation and Wiring

Effect of Transducer/Sensor and Cable Length Impedance on
Voltage Output Accuracy

For voltage outputs, the length of the cable used between the load
and the module can affect the accuracy of the data provided by the
module.

Voltage Output Accuracy

Where:

Rc = DC resistance of the cable (each conductor)
depending on cable length

Rs = Source impedance (1

Ω

)

Ri = Impedance of the voltage input

Vs = Voltage at the output of 1769-OF4 module

Vin = Measured potential at the module input

%Ai = Percent added inaccuracy in a voltage-based
system due to source and cable impedance

For example, for Belden 8761 two conductor, shielded cable and a
1769-IF4 input module as the load:

Rc = 52.5

Ω

/1000 m

Rs = 1

Ω

Ri = 220 K

Ω

Effect of Output Impedance and Cable Length on Accuracy

Length of Cable

DC Resistance of the Cable Rc

Accuracy Impact at the
Load

50 m (164 ft)

2.625

Ω

0.00284%

100 m (328 ft)

5.25

Ω

0.00523%

200 m (656 ft)

10.50

Ω

0.01%

300 m (984 ft)

15.75

Ω

0.01477%

V in

Vs

Ri

Rc

Rc

Rs

+

-

Vin

Ri

Vs

×

[

]

Rs

2

Rc

×

(

)

Ri

+

+

[

]

--------------------------------------------------------

=

%

Ai

1

Vin

Vs

---------

100

Ч

=

Advertising