Figure 4

The Output File For a Card Diagnostics Test

CARD DIAGNOSTICS

PASS:ą1

OF

2

Wed Aug 22 11:48:13 1990

Start/Stop 1784-KT2 Proce . . .

ąError: No error found.

NUM FAILS:

0

PASS/FAIL:

PASS

Dual Port (KT2 side) . . . . . . . .

ąError: No error found.

NUM FAILS:

0

PASS/FAIL:

PASS

Interrupts (PS2 to KT2) . . . . . .

ąError: No error found.

NUM FAILS:

0

PASS/FAIL:

PASS

Memory . . . . . . . . . . . . . . . . .

ąError Code: 128 RAM1 Failure.

NUM FAILS:

1

PASS/FAIL:

FAIL

Timer Operation . . . . . . . . . . .

ąError Code: 16 CTC Counter

ąMode Failure.

NUM FAILS:

1

PASS/FAIL:

FAIL

Serial Port Operation . . . . . . .

ąError: No error found.

NUM FAILS:

0

PASS/FAIL:

PASS

CARD DIAGNOSTICS

PASS:ą2

OF

2

Wed Aug 22 11:48:16 1990

Start/Stop 1784-KT2 Proce . . .

ąError: No error found.

NUM FAILS:

0

PASS/FAIL:

PASS

Dual Port (KT2 side) . . . . . . . .

ąError: No error found.

NUM FAILS:

0

PASS/FAIL:

PASS

Interrupts (PS2 to KT2) . . . . . .

ąError: No error found.

NUM FAILS:

0

PASS/FAIL:

PASS

Memory . . . . . . . . . . . . . . . . .

ąError: No error found.

NUM FAILS:

0

PASS/FAIL:

PASS

Timer Operation . . . . . . . . . . .

ąError: No error found.

NUM FAILS:

0

PASS/FAIL:

PASS

Serial Port Operation . . . . . . .

ąError: No error found.

NUM FAILS:

0

PASS/FAIL:

PASS

CARD DIAGNOSTICS

FINAL RESULTS

Wed Aug 22 11:48:17 1990

Start/Stop 1784-KT2 Proce. . . .

NUM FAILS:

0

PASS/FAIL:

PASS

Dual Port (KT2 side) . . . . . . . .

NUM FAILS:

0

PASS/FAIL:

PASS

Interrupts (PS2 to KT2) . . . . . .

NUM FAILS:

0

PASS/FAIL:

PASS

Memory . . . . . . . . . . . . . . . . .

NUM FAILS:

1

PASS/FAIL:

FAIL

Timer Operation . . . . . . . . . . .

NUM FAILS:

1

PASS/FAIL:

FAIL

Serial Port Operation . . . . . . .

NUM FAILS:

0

PASS/FAIL:

PASS

In the above example, the Card Diagnostics test was run twice. The timer
operation and the memory diagnostics show errors in the first pass of tests
and none in the second pass. The final results section indicates the failure
of both diagnostics from the first run of tests.