Building loopback connectors – Rockwell Automation 1784-KT2/C INST.DATA COMM.INTERFACE MOD. User Manual

Page 29

Advertising
background image

Communication Interface Module

Cat. No. 1784-KT2/C

Installation Data

29

This section shows you how to build the PLC–2 and PLC–3 loopback
connectors required for Off–Line Communications Diagnostics tests. Two
loopback tests are performed during an Off–Line Communications test. In
a loopback test, you download a program to the 1784–KT2 which:

transmits a packet of data
receives the same packet of data
verifies that the transmitted and received packets are identical

For more information on loopback tests, see the section entitled “The
Off–Line Communications Diagnostics Test.”

To build the PLC–2 and PLC–3 loopback connectors, you will need the
following items:

Table 6

Required Items for Building a Loopback Connector

Item:

Quantity:

AMP Part No.:

Connector housing

2

748367-1

Contact pins

16

748333-4

HandĆcrimp tool

1

90430-1

22-28 AWG wire

2 ft

(none)

Important: To ensure correct and reliable assembly, use the hand–crimp
tool with the AMP part number listed above.

Also, the maximum insulation diameter for each wire is 0.04”.

To build the PLC–2 and PLC–3 loopback connectors, follow the steps
below:

1.

Cut eight 3–inch sections of wire.

2.

Strip 0.2” of insulation off each end of wire.

3.

Using the crimp tool, crimp the contact pins onto each end of wire.

Building Loopback

Connectors