1-10 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Publication 1784-IN003D-EN-P - January 2006

Connect to a Device on the ControlNet Network

The 1786-CP cable (Figure 1.3) connects a host computer to another ControlNet
device. It has two RJ-45 8-pin connectors.

Figure 1.3 1786-CP cable

See Tables 1.1 and 1.2 for the wiring for the 1786-CP cable.

ATTENTION

Use only the 1786-CP cable when you connect a
programming terminal to the network through the Network
Acces Port (NAP). If you use a different cable, it could
result in possible network failures or product damage.

Table 1.1 Wiring For 1786-CP Cable (Connector 1)

Connector 1

Wire Number

Signal Mnemonic

Signal Name

1

ISO-GND

Isolated Ground

2

N.C.

No Connection

3

PTTX-H

Transmit Data High

4

PTTX-L

Transmit Data Low

5

PTRX-L

Receive Data Low

6

PTRX-H

Receive Data High

7

N.C.

No Connection

8

ISO-GND

Isolated Ground

RJ-45 8-pin Connectors

1786-CP Cable

30124-m

Connector 1

Connector 2

Advertising