Interpret the LED Indicators 6-3

Publication 1784-IN003D-EN-P - January 2006

Steady red

Faulted card

Check operating system event log for details
of fault (if the personal computer’s operating
system supports an event log)

Cycle power to the computer

Verify that you have firmly inserted the
1784-PCIC or 1784-PCICS card into a PCI local
bus expansion slot and that the expansion
slot screw is tightened

If fault persists, contact your Rockwell
Automation representative or distributor

Alternating red/green

Self-test

Incorrect channel
configuration

None

Verify that the ControlNet network is
connected to the correct channel of the
1784-PCIC or 1784-PCICS card (for example,
if the ControlNet network is configured for
channel A only, then the card must be
connected to the network via channel A)

Alternating red/off

Incorrect node
configuration

Duplicate
ControlNet node
address

Check 1784-PCIC or 1784-PCICS node
address and other ControlNet configuration
parameters

A or

B

Cause

Action

Off

Channel disabled

Use RSNetWorx for ControlNet sofware to
configure the ControlNet network for
redundant media, if required

Steady green

Normal operation

None

Flashing green/off

Temporary
network errors

Check media for broken cables, loose
connectors, or missing terminators

If condition persists, refer to the ControlNet
Media Planning and Installation Manual,
publication CNET-IN002

Flashing red/off

Media fault

Check media for broken cables, loose
connectors, or missing terminators

If condition persists, refer to the ControlNet
Media Planning and Installation Manual,
publication CNET-IN002

Table 6.1 ControlNet status interpretation