6-4 Interpret the LED Indicators

Publication 1784-IN003D-EN-P - January 2006

A or

B

Cause

Action

Flashing red/off

No other nodes
present on
network

Add other nodes to the network

Flashing red/green

Incorrect node
address

Change 1784-PCIC or 1784-PCICS node
address so that it is less than or equal to

UMAX

(1)

Stop and restart the 1784-PCIC or
1784-PCICS driver in RSLinx software

Incorrect network
configuration

Use RSNetWorx for ControlNet software to
reconfigure the ControlNet network so that

UMAX

(1)

is greater than or equal to the

1784-PCIC or 1784-PCICS node address

(1)

UMAX is the highest node address on a ControlNet network that can transmit data.