6-4 Interpret the LED Indicators
Publication 1784-IN003D-EN-P - January 2006
A or
B
Cause
Action
Flashing red/off
•
No other nodes
present on
network
•
Add other nodes to the network
Flashing red/green
•
Incorrect node
address
•
Change 1784-PCIC or 1784-PCICS node
address so that it is less than or equal to
UMAX
(1)
•
Stop and restart the 1784-PCIC or
1784-PCICS driver in RSLinx software
•
Incorrect network
configuration
•
Use RSNetWorx for ControlNet software to
reconfigure the ControlNet network so that
UMAX
is greater than or equal to the
1784-PCIC or 1784-PCICS node address
(1)
UMAX is the highest node address on a ControlNet network that can transmit data.