Wiring the Home Limit Switch Input

The home limit switch inputs to the servo module are designed for 24V dc
nominal operation. These inputs should be wired for current sourcing
operation.

Figure 9 Home Limit Switch Input

Wiring the OK Contacts

A set of isolated solid- state OK relay contacts is provided for optional
interface to an E- stop string, which controls power to the associated pumps.
The OK contacts are rated to drive an external 24V dc pilot relay (for
example, Allen-Bradley 700- HA32Z24) whose contacts can be incorporated
into the E- Stop string as in the following figure.

Figure 10 Wiring OK Contacts

From
1756-M02AS

HOME

IN_COM

24 V dc

Power

Supply
+

43396

General cable
C0720

From
1756-M02AS

+OK
-OK

24 V dc

Power

Supply
+

43397

OK Pilot
Relay

43398

OK Pilot
Relay
Contacts

Start

Stop

CR1

CR1

CR1

M1

24V ac/dc or
120V ac
typical

General cable
C0720