Rockwell Automation 1756-M02AS Motion Module Installation Instructions User Manual

Page 19

Advertising
background image

SSI Servo Module 19

Publication

1756-IN595A-EN-P - March 2004

Removing the Removable Terminal Block from the Module

If you must remove the module, you have to remove the RTB first.

Flashing red
light

The axis drive output is in
the shutdown state.

• Check for faults that may have

generated this state.

• Execute the Motion Axis

Shutdown Reset instruction.

• Resume normal operation.

Steady red light

The axis drive is faulted.

• Check the drive status.
• Clear the Drive Fault condition

at the drive.

• Clear the servo fault condition

using the Motion Axis Fault
Reset instruction.

• Resume normal operation.
• Check the configuration for the

Drive Fault.

• If configured to be normally

open and there is no voltage,
this is the normal condition.

• If configured to be normally

closed and 24V dc is applied,
this is the normal condition.

WARNING

When you connect or disconnect the Removable Terminal Block
(RTB) with field side power applied; an electrical arc can occur.
This could cause an explosion in hazardous location
installations.
Be sure that power is removed or the area is nonhazardous
before proceeding.

If the DRIVE
LED displays:

The module status is:

Take this action: