Rockwell Automation 1756-M02AS Motion Module Installation Instructions User Manual
Page 15
 
SSI Servo Module 15
Publication
1756-IN595A-EN-P - March 2004
The table below provides an explanation of the OK indicator.
If the OK LED 
displays:
The module status is:
Take this action:
Off
The module is not operating.
• Apply chassis power.
• Verify the module is completely 
inserted in chassis and 
backplane.
Flashing green 
light
The module has passed 
internal diagnostics, but it is 
not communicating axis 
data over the backplane.
• None, if you have not
configured the module.
• If you have configured the
module, check the slot number 
in the 1756-M02AS Properties 
dialog box.
Steady green 
light
One of the following:
• Module is
exchanging axis 
data.
• The module is in
the normal 
operating state.
None
Flashing red 
light
One of the following:
• A major
recoverable failure 
has occurred.
• A communication
fault, timer fault, 
or non-volatile 
memory storage 
(NVS) update is in 
progress.
• The OK contact
has opened.
If an NVS update is in progress, 
complete the NVS update.
If an NVS update is not in progress:
• Check the Servo Fault word for
the source of the error.
• Clear the servo fault condition
via Motion Axis Fault Reset 
instruction.
• Resume normal operation.
• If the flashing persists, 
reconfigure the module.