Module status using the drive indicator – Rockwell Automation 1756-M02AS Motion Module Installation Instructions User Manual

Page 17

Advertising
background image

SSI Servo Module 17

Publication

1756-IN595A-EN-P - March 2004

Module Status Using the DRIVE Indicator

Figure 15 Drive Indicator LED

Flashing red
light

The axis servo loop error
tolerance has been
exceeded.

• Correct the source of the

problem.

• Clear the servo fault condition

using the Motion Axis Fault
Reset instruction.

• Resume normal operation.

Steady red light

An axis SSI feedback fault
has occurred.

• Correct the source of the

problem by checking the SSI
device and power connections.

• Clear the servo fault condition

using the Motion Axis Fault
Reset instruction.

• Resume normal operation.

If the FDBK
LED displays:

The module status is:

Take this action:

CH0 CH1

FDBK

DRIVE

OK

2 AXIS SERVO / SSI

FDBK

DRIVE

Drive
indicators

Advertising