Module status using the fdbk indicator, Figure 14 fdbk indicator led – Rockwell Automation 1756-M02AS Motion Module Installation Instructions User Manual

Page 16

Advertising
background image

16 SSI Servo Module

Publication

1756-IN595A-EN-P - March 2004

Module Status Using the FDBK Indicator

Figure 14

FDBK Indicator LED

The table below provides an explanation of the FDBK indicator.

Steady red light

One of the following:

• A potential non-

recoverable fault
has occurred.

• The OK contact

has opened.

• Reboot the module.
• If the solid red persists, replace

the module.

If the FDBK
LED displays:

The module status is:

Take this action:

Off

The axis is not used.

• None, if you are not using this

axis.

• If you are using this axis, make

sure the module is configured
and an axis tag has been
associated with the module.

Flashing green
light

The axis is in the normal
servo loop inactive state.

None. The servo axis state can be
changed by executing motion
instructions.

Steady green
light

The axis is in the normal
servo loop active state.

None. The servo axis state can be
changed by executing motion
instructions.

If the OK LED
displays:

The module status is:

Take this action:

CH0 CH1

FDBK

DRIVE

OK

2 AXIS SERVO / SSI

FDBK

DRIVE

Feedback
indicators