Rockwell Automation 1756-M02AS Motion Module Installation Instructions User Manual

Page 23

Advertising
background image

SSI Servo Module 23

Publication

1756-IN595A-EN-P - March 2004

Isolation Voltage

User to System

30V continuous

RTB keying

User-defined

Field wiring arm

36-position RTB (1756-TBCH or -TBS6H)

(1)

RTB screw torque (cage clamp)

4.4 inch-pounds (0.4Nm) maximum

Conductors

Wire size

Category

#22 to #14 AWG (0.324 to 2.08 sq. mm) stranded

(1)

3/ 64 inch (1.2 mm) insulation maximum

2

(2)

Screwdriver blade width for RTB

1/8 inch (3.2mm) maximum

Environmental Conditions

Operating Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0 to 60°C (32 to 140°F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating
Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating
Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating
Thermal Shock):
–40 to 85°C (–40 to 185°F)

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged Non-operating
Damp Heat):
5 to 95% non-condensing

Vibration

IEC60068-2-6 (Test Fc, Operating):
2g @ 10-500Hz

Shock

IEC60068-2-27 (Test Ea, Unpackaged shock):
Operating 30g
Non-operating 50g

Emissions

CISPR 11:
Group 1, Class A