12 SmartGuard 600 Controllers

Publication 1752-IN001C-EN-P - January 2009

Power Supply Connections

Wiring the SmartGuard 600 Controller

See

page 24

for appropriate wire size and torque specifications.

Controller Terminal Descriptions

Terminal Designation

Description

V0

Power terminal for internal circuit (logic).

G0

Power terminal for internal circuit (logic).

V1

Power terminal for input circuits and test outputs.

G1

Power terminal for input circuits and test outputs.

V2

Power terminal for safety outputs.

G2

Power terminal for safety outputs.

IN0…IN15

Terminals for safety inputs.

T0…T3

These are test output terminals that can provide pulse test sources for safety
inputs IN0...IN15. T3 can also support wire off detection and burned out bulb
detection for a load such as a muting lamp.

OUT0…OUT7

Terminals for safety outputs.

WARNING

If you connect or disconnect wiring while the field-side power is applied, an electrical arc
can occur. This could cause an explosion in hazardous location installations. Be sure that
power is removed or the area is nonhazardous before proceeding.

+ -

+ -

+ -