8 SmartGuard 600 Controllers

Publication 1752-IN001C-EN-P - January 2009

Set the communication rate by using the DIP switch on the front of the controller.

Set the IP Address for Ethernet Communication

Connect the 1752-L24BBBE controller to the network via a 100 Mbps Ethernet
switch, which will help reduce collisions and lost packets, and increase bandwidth.

The 1752-L24BBBE controller is shipped with BOOTP enabled for setting the IP
address. You can use any commercially available BOOTP server. If you do not have
BOOTP Server capabilities on your network, download the free Rockwell
Automation BOOTP server from

http://www.ab.com/networks/bootp.html

.

To set the IP address by using the Rockwell Automation BOOTP utility, follow
these steps.

1. Run the BOOTP utility.

2. Double-click the hardware address of the device you want to configure.

DIP Switch Settings

DIP Switch

Pin

1

2

3

4

Communication Rate

OFF

OFF

OFF

OFF

125 Kbps

ON

OFF

OFF

OFF

250 Kbps

OFF

ON

OFF

OFF

500 Kbps

ON

ON

OFF

OFF

Set by software

ON or OFF

ON or OFF

ON

OFF

Set by software

ON or OFF

ON or OFF

ON or OFF

ON

Automatic baud-rate detection

IMPORTANT

If you change the communication rate of your network, make sure that all devices change
to the new communication rate. Mixed communication rates produce communication
errors.