SmartGuard 600 Controllers 19

Publication 1752-IN001C-EN-P - January 2009

3. Contact Rockwell Automation.

If your Module Status indicator is flashing red, follow these steps.

1. Configure the switches properly.

2. Reset the configuration data.

If your Module Status indicator is solid red (on), follow these steps.

1. Cycle the power supply.

2. Check external wiring.

3. Take corrective actions for noise.

4. Contact Rockwell Automation.

If your Module Staus indicator is flashing red and green, follow these steps.

1. Configure the switches properly.

2. Set the safety network number.

3. Reconfigure the device.

DeviceNet Network Status (NS D) Indicator Descriptions

If the DeviceNet
Network Status
(NS D) indicator is

It means

Take this action

Off

The controller is not online or may not
have power from the DeviceNet
network.

Refer to the corrective action following this
table.

Green, on

The controller is online; connections
are established.

No action required.

Green, flashing

The controller is online; no
connections are established.

Red, on

Communication failure due to
duplicate MAC ID (error code F0) or
Bus OFF (error code F1).

Refer to the corrective action following this
table

Red, flashing

Communication timeout.

Red/green flashing

The Safety Network Number (SNN) is
being set.

No action required.