20 SmartGuard 600 Controllers

Publication 1752-IN001C-EN-P - January 2009

If your Network Status indicator is off, follow these steps.

1. Cycle the power supply.

2. Check external wiring.

3. Take corrective actions for noise.

4. Contact Rockwell Automation.

If your Network Status indicator is on or flashing red, follow these steps.

1. View the Alphanumeric display for the node address of the error and error

code.

2. Check that node addresses have not been duplicated.

3. Make sure the communication rate is the same for all nodes.

4. Check that cables are not loose, disconnected or too long.

5. Verify that terminating resistors have been installed only at both ends of the

main line.

6. Take corrective action for noise.

7. Make sure target devices are configured, verified, and in normal operating

state.

Lock Configuration (Lock) Status Indicator Descriptions

If the Lock
Configuration (Lock)
status indicator is

It means

Take this action

Yellow, on

A locked valid configuration exists.

No action required.

Yellow, flashing

An unlocked valid configuration exists. Lock the configuration before operating the

safety system.

Off

The configuration is invalid.

Reconfigure the controller.