Connect to the devicenet port, Connecting to the usb port – Rockwell Automation 1752-L24BBBE SmartGuard 600 Controllers Installation User Manual

Page 16

Advertising
background image

16 SmartGuard 600 Controllers

Publication 1752-IN001C-EN-P - January 2009

Connect to the DeviceNet Port

Follow these steps to connect to the DeviceNet port.

1. Wire the connector according to the colors on the connector.

2. Attach the connector to the DeviceNet port.

3. Tighten the screws to 0.25…0.3 N•m (2.21…2.65 lb•in).

For detailed DeviceNet connection information, refer to the DeviceNet Media
Design Installation Guide, publication

DNET-UM072

. Also refer to the Industrial

Automation Wiring and Grounding Guidelines, publication

1770-4.1

.

Connecting to the USB Port

Connect the USB communication connector to your personal computer when you
want to configure the network and controller by using RSNetWorx for DeviceNet
software. Use a commercially available USB-A to USB-B male/male cable to make
the connection.

Wire No.

Wire Color

Connects to

1

Red

V+

2

White

CAN H

3

Drain

4

Blue

CAN L

5

Black

V-

ATTENTION

The USB cable length must be less than 3 m (10 ft).

The USB port is intended for temporary programming purposes only and is not intended for
permanent connection.

WARNING

If you connect or disconnect the USB cable with power applied to this module or any
device on the USB network, an electrical arc could occur. This could cause an explosion in
hazardous location installations. Be sure that power is removed or the area is
nonhazardous before proceeding.

D

D

D

D

D

1

2

3

4

5