Rockwell Automation 1752-L24BBBE SmartGuard 600 Controllers Installation User Manual

Page 27

Advertising
background image

SmartGuard 600 Controllers 27

Publication 1752-IN001C-EN-P - January 2009

EFT/B immunity

IEC 61000-4-4:

±2 kV @ 5 kHz on power
ports

±2 kV @ 5 kHz on signal
ports

±2 kV @ 5 kHz on
communication ports

IEC 61000-4-4:

±2 kV @ 5 kHz on power
ports

±1 kV @ 5 kHz on signal
ports

±1 kV @ 5 kHz on
communication ports

Surge transient immunity

IEC 61000-4-5:

±1 kV line-line (DM) and ±2
kV line-earth (CM) on power
ports

±1 kV line-line (DM) and ±2
kV line-earth (CM) on signal
ports

±1 kV line-earth (CM) on
communication ports

IEC 61000-4-5:

±500V line-line (DM) and ±1
kV line-earth (CM) on power
ports

±1 kV line-earth (CM) on
signal ports

±1 kV line-earth (CM) on
communication ports

Conducted RF immunity

IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications

Certification

(1)

(when product is marked)

Value

c-UL-us

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified
for US and Canada. See UL File E194810.

CE

European Union 2004/108/EEC EMC Directive, compliant with:

EN 61000-6-4; Industrial Emissions

EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

EN 61326-1; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

C-Tick

Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions

TÜV

TÜV Certified for Functional Safety
Functional Safety: SIL 1 to 3, according to IEC 61508; Performance Level PL(e)
according to ISO 13849-1, Category 1 to 4, according to EN954-1; NFPA79;
when used as described in the SmartGuard Controllers Safety Reference
Manual, publication

1752-RM001

.

UL

UL Certified for Functional Safety. See UL File E256621.

Environmental Specifications

Attribute

1752-L24BBB

1752-L24BBBE

Advertising