Rockwell Automation 1752-L24BBBE SmartGuard 600 Controllers Installation User Manual

Page 26

Advertising
background image

26 SmartGuard 600 Controllers

Publication 1752-IN001C-EN-P - January 2009

Environmental Specifications

Attribute

1752-L24BBB

1752-L24BBBE

Temperature, storage

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…70 °C (-40…158 °F)

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-10…55 °C (14…131 °F) (surrounding air temperature)

Relative humidity

IEC 60068-2-30
(Test Db, Unpackaged Nonoperating Damp Heat):
10…95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):
0.35 mm @ 10…57 Hz
5 g @ 57…150 Hz

IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock): 15 g

Shock, nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock): 30 g

Enclosure type rating

Meets IP20

Emissions

CISPR 11: Group 1, Class A

ESD immunity

IEC 61000-4-2:

4 kV contact discharges

8 kV air discharges

IEC 61000-4-2:

6 kV contact discharges

8 kV air discharges

Radiated RF immunity

IEC 61000-4-3:

10 V/m with 1 kHz
sine-wave 80% AM from
80…1000 MHz

10 V/m with 1 kHz
sine-wave 80% AM from
1.4…2.0 GHz

10 V/m with 200 Hz 50%
Pulse 100% AM at 900 MHz

10 V/m with 200 Hz 50%
Pulse 100% AM at 1200
MHz

3 V/m with 1 kHz sine-wave
80% AM from 2000…2700
MHz

IEC 61000-4-3:

10 V/m with 1 kHz
sine-wave 80% AM from
80…1000 MHz

10 V/m with 1 kHz
sine-wave 80% AM from
1.4…2.0 GHz

20 V/m with 200 Hz 50%
Pulse 100% AM at 800, 900,
1200 MHz

3 V/m with 1 kHz sine-wave
80% AM from 2000…2700
MHz

Advertising
This manual is related to the following products: