Table 36, Table 37, And m – Rockwell Automation 1791DS-IBxxxx Guard I/O DeviceNet Safety Modules User Manual

Page 163

Advertising
background image

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

163

Safety Data

Appendix B

Table 36 - Probability of Failure Data (IEC 61508, Edition 2, 2010)

Table 37 - Probability of Failure Data (IEC 61508, Edition 1, 1999)

Cat. No.

Description

Calculated PFD

2 Years
(17,520
hours)

5 Years
(43,800
hours)

10 Years
(87,600
hours)

20 Years
(175,200
hours)

PFH
(1/hour)

Spurious Trip
Rate (SPR)

MTTF
(years)

1791DS-IB8XOBV4

CIP Safety 8-point
input/4 bi-polar
output module

4.16E-06

1.04E-05

2.08E-05

4.16E-05

5.02E-10

5.608E-06

20.34

1791DS-IB16

CIP Safety 16-point
input module

4.11E-06

1.03E-05

2.06E-05

4.11E-05

4.96E-10

3.301E-06

34.56

1732DS-IB8XOBV4

CIP Safety 8-point
input/4 bi-polar
output module

4.16E-06

1.04E-05

2.08E-05

4.16E-05

5.02E-10

5.608E-06

20.34

1732DS-IB8

CIP Safety 8-point
input module

4.11E-06

1.03E-05

2.06E-05

4.11E-05

4.96E-10

3.301E-06

34.56

Cat. No.

Description

Calculated PFD

2 Years
(17,520
hours)

5 Years
(43,800
hours)

10 Years
(87,600 hours)

20 Years

(1)

(175,200 hours)

PFH
(1/hour)

(1)

(1)

The 20-year PFD data for this product applies only to product with a manufacture date code of 2009/
01/01 (January 1, 2009) or later. See the product label for the date code.

1791DS-IB12

CIP Safety 12-point
input module

1.754E-06

4.419E-06

8.962E-06

6.013E-06

6.84E-11

1791DS-IB8XOB8

CIP Safety 8-point
input/8-point output
module

1.755E-06

4.421E-06

8.963E-06

6.013E-06

6.84E-11

1791DS-IB4XOW4

CIP Safety 4-point
input/4-point relay
output module

4.151E-05

1.207E-04

2.978E-04

7.684E-04

4.072E-09