Module Tags

Fault and Status Reporting
Between the Module
and Controllers

The 1732E ArmorBlock EtherNet/IP Dual Port 8-Point Sequence of Events
Input and Scheduled Output Modules modules send fault/status data to the
owner-controller. The module maintains a Module Fault Word, the highest level
of fault reporting.

The following table describes the tag that can be examined in ladder logic to
indicate when a fault has occurred for your module:

• If a communication fault occurs on the module, all 32 bits in the Module

Fault Word are set to 1.

Module Tag Names and
Definitions

The 1732E-IB8M8SOER and 1732E-OB8M8SR has three sets of tags:

• Configuration
• Input
• Output

Tags Used

Configuration, Input and Output Tags for 1732E-IB8M8SOER

The following table describes the configuration tags generated in RSLogix 5000
software when you use your 1732E-IB8M8SOER module.

Tag

Description

Module Fault Word

This word provides fault summary reporting. The tag name is Fault.

Module Fault Word

42676

Bit 31

Bit 0

A communications fault sets all bits in the Module Fault Word.

Configuration Tags – 1732E-IB8M8SOER

Tag Name

Type

Description

C

.

FilterOffOn

INT

Sets the OFF to ON filter time for all 8 inputs. Times are set in

µs increments of 0, 1000 (default),

2000, 4000, 8000 and 16000

µs.

0 = no filtering
For more information on Software Configurable Input Filters, see

page 55

.