Rockwell Automation 1732E-OB8M8SR EtherNet/IP Dual Port 8-Point SOE Input and Scheduled Output Modules UM User Manual
Page 116

106
Rockwell Automation Publication 1732E-UM003B-EN-E - March 2014
Appendix C Data Tables
Configuration Assembly Instance 124 Data Structure (Configuration Header)
Configuration Byte Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Reserved (Ignored)
CRN
1
Reserved (Ignored)
2
Reserved (Ignored)
3
Reserved (Ignored)
CRN
Configuration Revision Number
Assembly Instance 4 Data Structure
Produced Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
In 7
In 6
In 5
In 4
In 3
In 2
In 1
In 0
Assembly Instance 34 Data Structure
Consumed Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Out 7
Out 6
Out 5
Out 4
Out 3
Out 2
Out 1
Out 0
Assembly Instance 111 Data Structure
Consumed
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
4
Group 0 Input OFF_ON Delay Filter (Low Byte)
5
Group 0 Input OFF_ON Delay Filter (High Byte)
6
Group 0 Input ON_OFF Delay Filter (Low Byte)
7
Group 0 Input ON_OFF Delay Filter (High Byte)
8
Reserved (Ignored)
Master
Sync
Enable
Latch
Events
9
Capture
OffOn7
Capture
OffOn6
Capture
OffOn5
Capture
OffOn4
Capture
OffOn3
Capture
OffOn2
Capture
OffOn1
Capture
OffOn0
10
Capture
OnOff7
Capture
OnOff7
Capture
OnOff7
Capture
OnOff7
Capture
OnOff7
Capture
OnOff7
Capture
OnOff7
Capture
OnOff7
11
Reserved (Ignored)
Where:
MasterSyncEnable – This is a PTP enable bit which indicates if the module is expected to synch
to a master clock. If not enabled (0), then the Module LED does not flash green if not synched to a
master clock. Disabling the bit does not prevent the module from synchronizing to a master clock.
LatchEvents – When set, latches events means that an event is not overwritten until
acknowledged. In Per Point mode, a sequence of events of LO, HI, LO will cause the first LO and HI
transitions to be recorded and the final LO to be ignored. All subsequent transitions on that point
will be ignored until acknowledged/reset. If the bit is not set, the new LO will overwrite the first
LO event immediately, even if the controller has yet to extract that data. In FIFO mode, when set
events will not be erased from the FIFO until read.
CaptureOffOn – Enables capturing Off to On events on a per point basis. If cleared, that point will
not record Off to On events. Useful to not use up buffer space on events user does not care about.
CaptureOnOff – Enables capturing On to Off events on a per point basis. If cleared, that point will
not record On to Off events. Useful to not use up buffer space on events user does not care about.