Where:

FIFO Mode
EventAck
– The controller writes back the EventNumber read to transition buffers. All events with EventNumbers less than or
equal to the EventAck will be acknowledged. If the RetreiveByPoint bit is set the PointToRetrieve attribute must also be used to
specify the point to retrieve next.
NewDataAck – Forces NewData bits clear even if all the timestamps for that point have not been acknowledged. Also clears
the EventOv bits.
PointToRetrieve – When RetrieveByPoint is set, determines point requested for events to be returned. Allows a user to query
events in the sequence they happened by point instead of the overall sequence the events occurred.
RetrieveByPoint – Changes retrieval mechanism from sequential (when 0) to retrieving events on a per point basis according
to value set in PointToRetrieve field.
Per Point Mode
EventAck
– Is a 0 or 1 to indicate acknowledging an OnOff or OffOn event respectively, or a 2 to acknowledge both.
NewDataAck – Acknowledges the corresponding inputs timestamp and clears its NewData and EventOv bits.
PointToRetrieve – Not used.
RetrieveByPoint – Not used.
Reset Events – When transitioned from 0 to 1, erases all recorded time stamped events.

Configuration Assembly Instance 163 Data Structure

Consumed
Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

4

Group 0 Input OFF_ON Delay Filter (Low Byte)

5

Group 0 Input OFF_ON Delay Filter (High Byte)

6

Group 0 Input ON_OFF Delay Filter (Low Byte)

7

Group 0 Input ON_OFF Delay Filter (High Byte)

8

Reserved (Ignored)

IV_G0

IA_G0

FV_G0

FA_G0

9

Reserved (Ignored)

Where:

FA_G0 = Fault Action Group 0 (0 = Apply Fault Value; 1= Hold Last State)
IA_G0 = Idle Action Group 0 (0 = Apply Fault Value; 1= Hold Last State)
FV_G0 = Fault Value Group 0 (0 = OFF;1 = ON)
IV_G0 = Idle Value Group 0 (0 = OFF;1 = ON)

Configuration Assembly Instance 171 Data Structure

Consumed
Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Reserved (Ignored)

CRN

1

Reserved (Ignored)

ProgTo
FaultEn

2

FaultMode
Ch7

FaultMode
Ch6

FaultMode
Ch5

FaultMode
Ch4

FaultMode
Ch3

FaultMode
Ch2

FaultMode
Ch1

FaultMode
Ch0

3

Reserved (Ignored)

4

FaultVal
Ch7

FaultVal
Ch6

FaultVal
Ch5

FaultVal
Ch4

FaultVal
Ch3

FaultVal
Ch2

FaultVal
Ch1

FaultVal
Ch0

5

Reserved (Ignored)

6

FaultFinal
State Ch7

FaultFinal
State Ch6

FaultFinal
State Ch5

FaultFinal
State Ch4

FaultFinal
State Ch3

FaultFinal
State Ch2

FaultFinal
State Ch1

FaultFinal
State Ch0

7

Reserved (Ignored)

Consumed Assembly Instance 159 Data Structure

Consumed
Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Advertising