112

Rockwell Automation Publication 1732E-UM003B-EN-E - March 2014

Appendix C Data Tables

8

ProgMode
Ch7

ProgMode
Ch6

ProgMode
Ch5

ProgMode
Ch4

ProgMode
Ch3

ProgMode
Ch2

ProgMode
Ch1

ProgMode
Ch0

9

Reserved (Ignored)

10

ProgVal
Ch7

ProgVal
Ch6

ProgVal
Ch5

ProgVal
Ch4

ProgVal
Ch3

ProgVal
Ch2

ProgVal
Ch1

ProgVal
Ch0

11

Reserved (Ignored)

12…15

Hold Last State Duration [0]

16…19

Hold Last State Duration [1]

20…23

Hold Last State Duration [2]

24…27

Hold Last State Duration [3]

28…31

Hold Last State Duration [4]

32…35

Hold Last State Duration [5]

36…39

Hold Last State Duration [6]

40…43

Hold Last State Duration [7]

Where:

ProgToFaultEn – Selects whether (enabled) or not (disabled) to apply the fault value when the output is already being set to
the program value when a Fault (connection timeout) occurs in Program Mode.
FaultMode – If Fault occurs (connection loss): When clear use FaultValue for Output. When set, Output Holds Last State for
HoldLastStateDuration.
Fault Value – If corresponding FaultMode bit clear, defines Output Value on Fault (connection timeout). Not used if FaultMode
bit is set.
Hold Last State Duration – If FaultMode is set (Hold Last State), this value determines the length of time the last state is to
be held prior to the FaultFinalState being applied. Valid values are 0 = Hold Forever, and either 1, 2, 5, or 10 (indicating hold
time in seconds). All other values reserved.
FaultFinalState – If FaultMode is set (Hold Last State) and HoldLastStateDuration[8] is non-zero, determines the final Output
state after the configured time out occurs.
ProgMode – If ProgramMode event occur: When clear use ProgValue for Output.
When set, Output Holds Last State.
ProgValue – If corresponding ProgMode bit clear, defines Output value on Program Mode.
Not used if ProgMode bit set.

Consumed Assembly Instance 174 Data Structure

Consumed
Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Data Ch7

Data Ch6

Data Ch5

Data Ch4

Data Ch3

Data Ch2

Data Ch1

Data Ch0

1

Reserved (Ignored)

2

ScheduleMa
sk
Ch7

Schedule
Mask
Ch7

Schedule
Mask
Ch7

Schedule
Mask
Ch7

Schedule
Mask
Ch7

Schedule
Mask
Ch7

Schedule
Mask
Ch7

Schedule
Mask
Ch0

3

Reserved (Ignored)

4

Timestamp Offset

5

Schedule Timestamp

6

Schedule[0].ID

7

Schedule[0].SequenceNumber

8

Schedule[0].OutputPointSelect

9

Schedule[0].Data

Configuration Assembly Instance 171 Data Structure

Consumed
Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0