Create the example application, Configure your i/o module – Rockwell Automation 1732E-OB8M8SR EtherNet/IP Dual Port 8-Point SOE Input and Scheduled Output Modules UM User Manual

Page 45

Advertising
background image

Rockwell Automation Publication 1732E-UM003B-EN-E - March 2014

35

Configure the Module Using RSLogix 5000 Software Chapter 6

Create the
Example Application

Perform the following steps to create the example application:

1.

From the File menu, select New.

The New Controller dialog opens.

2.

Enter an appropriate name for the Controller, for example,
ArmorBlock_IO_Controller.

3.

Select the correct version, chassis type, and slot number of the controller,
and the folder where you want to save the RSLogix 5000 software file
(Create In). The Description is optional.

To use redundancy in your system, select the Redundancy Enabled
checkbox.

4.

Click OK.

Configure Your I/O Module

You must configure your module upon installation. The module will not work
until it has been configured with at least the default configuration.