Remove the Finger-safe
Terminal Block

When wiring field devices to the module, it is not necessary to remove
the terminal block. If you remove the terminal block, use the write-on
label on the side of the terminal block to identify the module slot
location and type. RTB position (for one-and-a-half size modules) can
be indicated by circling either the R for right side or L for left side.

Finger-safe Terminal Block

To remove the terminal block, loosen the upper and lower retaining
screws. The terminal block will back away from the module as you
remove the screws. When replacing the terminal block, torque the
retaining screws to 0.46 N•m (4.1 lb•in).

Wire the Finger-safe
Terminal Block

When wiring the terminal block, keep the finger-safe cover in place.

1. Loosen the terminal screws to be wired.

2. Begin wiring at the bottom of the terminal block and move up.