Chapter 3 Module Data, Status, and Channel Configuration

Bit Definitions for Input Channel Configuration Words

Define

To choose

Make these bit settings

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Input Filter Selection/
-3 dB Frequency

60 Hz

0

0

0

0

50 Hz

0

0

0

1

5 Hz

0

0

1

0

10 Hz

0

0

1

1

100 Hz

0

1

0

0

250 Hz

0

1

0

0

500 Hz

0

1

1

0

1000 Hz

0

1

1

1

No Filter

1

0

0

0

Enable Interrupt

(1)

(2)

(EI)

Enable

1

Disable

0

Process Alarm Latch

(2)

(AL)

Enable

1

Disable

0

Enable Process Alarms
(EA)

Enable

1

Disable

0

Enable Channel (EC)

Enable

1

Disable

0

(1) Alarm interrupts are not supported by all bus masters. Check your controller’s user manual to determine if expansion I/O interrupts are supported.
(2) Do not set this bit to 1 unless the Enable Process Alarms (EA) bit is also set to 1 for the same channel.

Bit Definitions for Input Range and Input Data Configuration Words

Define

To choose

Make these bit settings

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Input
Type/Range
Select

-10…10V DC

0

0

0

0

0…5V DC

0

0

0

1

0…10V DC

0

0

1

0

4…20 mA

0

0

1

1

1…5V DC

0

1

0

0

0…20 mA

0

1

0

1

Input Data
Format Select

Raw/Proportional
Counts

0

0

0

Engineering Units

0

0

1

Scaled for PID

0

1

0

Percent Range

0

1

1