Publication 1769-UM019A-EN-P - October 2008

Appendix A Specifications

Input Specifications

Attribute

Value

Analog normal operating ranges

(1)

±10V DC
0…10V DC

0…5V DC
1…5V DC

0…20 mA
4…20 mA

Full scale analog ranges

(1)

±10.5V DC
-0.5…10.5V DC

-0.5…5.25V DC
0.5…5.25V DC

0…21 mA
3.2…21 mA

Number of inputs

4 differential or single-ended

Converter type

Successive Approximation

Response speed per channel

Input filter and configuration dependent

Resolution, max

(2)

14 bits (unipolar)
14 bits plus sign (bipolar)

Rated working voltage

(3)

30V AC/30V DC

Common mode voltage range

(4)

±10V DC max per channel

Common mode rejection

Greater than 70 dB at 50 and 60 Hz with the 10 Hz filter selected, respectively

Input impedance, voltage terminal

220 k

Ω

Input impedance, current terminal

250

Ω

Overall accuracy, voltage terminal

(5)

0.15% full scale @ 25 °C (77 °F)

Overall accuracy, current terminal

(5)

0.2% full scale @ 25 °C (77 °F)

Accuracy drift with temperature, voltage terminal

±0.003% per °C

Accuracy drift with temperature, current terminal

±0.0045% per °C

Calibration

None required

Non-linearity (in percent full scale)

±0.03%

Repeatability

(6)

±0.03%

Module error over full temperature range 0…60 °C
(32…140 °F), voltage

0.2%

Module error over full temperature range 0…60 °C
(32…140 °F), current

0.3%

Channel diagnostics

Over- or under-range by bit reporting, process alarms

Max overload at input terminals, voltage

(7)

±30V DC continuous, 0.1 mA

Max overload at input terminals, current

(7)

±32 mA continuous, ±7.6V DC

Input group to bus isolation

500V AC or 710V DC for 1 minute (qualification test)
30V AC/30V DC working voltage (IEC Class 2 reinforced insulation)

(1) The over- or under-range flag will come on when the normal operating range (over/under) is exceeded. The module will continue to convert the analog input up to the

maximum full scale range. The flag automatically resets when within the normal operating range.

(2) Resolution is dependent upon your filter selection.
(3) Rated working voltage is the maximum continuous voltage that can be applied at the input terminal, including the input signal and the value that floats above ground

potential (for example, 10V DC input signal and 20V DC potential above ground).

(4) For proper operation, the plus input terminals must be within ±10V DC of analog common.
(5) Includes offset, gain, non-linearity and repeatability error terms.
(6) Repeatability is the ability of the input module to register the same reading in successive measurements for the same input signal.
(7) Damage may occur to the input circuit if this value is exceeded.