Invalid input range selected – Rockwell Automation 1769-IF4FXOF2F Compact Combination Fast Analog I/O Module User Manual

Page 64

Advertising
background image

64

Publication 1769-UM019A-EN-P - October 2008

Chapter 4 Module Diagnostics and Troubleshooting

Invalid Input Range Selected

These error codes occur when the 4-bit input range code for the
indicated channel is not one of the assigned input range codes for the
module.

See

Bit Definitions for Input Range and Input Data Configuration

Words on page 42

for details on the assigned input range codes for

each module.

X40D

010

0 0000 1101

Invalid alarm data (channel 0)

X40E

010

0 0000 1110

Invalid alarm data (channel 1)

X40F

010

0 0000 1111

Invalid alarm data (channel 2)

X410

010

0 0001 0000

Invalid alarm data (channel 3)

X411

010

0 0001 0001

Invalid input filter selected (channel 0)

X412

010

0 0001 0010

Invalid input filter selected (channel 1)

X413

010

0 0001 0011

Invalid input filter selected (channel 2)

X414

010

0 0001 0100

Invalid input filter selected (channel 3)

X415

010

0 0001 0101

Invalid output range selected (channel 0)

X416

010

0 0001 0110

Invalid output range selected (channel 1)

X417

010

0 0001 0111

Invalid output format selected (channel 0)

X418

010

0 0001 1000

Invalid output format selected (channel 1)

X419

010

0 0001 1001

Invalid output fault value selected (channel 0)

(2)

X41A

010

0 0001 1010

Invalid output fault value selected (channel 1)

(2)

X41B

010

0 0001 1011

Invalid output program/idle value selected (channel 0)

(2)

X41C

010

0 0001 1100

Invalid output program/idle value selected (channel 1)

(2)

X41D

010

0 0001 1101

Invalid output clamp value selected (channel 0)

X41E

010

0 0001 1110

Invalid output clamp value selected (channel 1)

X41F

010

0 0001 1111

Invalid ramp rate selected (channel 0)

(2)

X420

010

0 0010 0000

Invalid ramp rate selected (channel 1)

(2)

X421

010

0 0010 0001

Invalid real time sample value

(1) X represents the Don’t Care digit. Module configuration error codes are typically presented in their Hex Equivalent by the programming software.

(2) Some controllers do not support alternate output states. Refer to your controller user manual to determine whether alternate output states and these associated functions

are supported.

Extended Error Codes for Configuration Errors

Hex Equivalent

(1)

Module

Error Code

Extended Error

Information Code

Error Description

Binary

Binary