Module Data, Status, and Channel Configuration Chapter 3

If configured, ramping takes place only when the output is
commanded to go to a fault state. Ramping does not occur during
normal run operation.

The ramp rate values are entered in the Configuration Data file and
are accepted as valid only if:

the number of counts entered for a channel’s ramp rate is
greater than or equal to a minimum of 1% of the total number of
full scale counts for the channel’s selected data format.

the number of counts entered for a channel’s ramp rate is equal
to zero and ramping is not enabled for that channel.

Output Type/Range Selection

This selection lets you configure each output channel individually and
provides the means of designating whether the output is a voltage or
current source. The output range for each output channel is also
configured by this selection.

Percent of Full Scale

-10…10V DC

21,000

208

0.20V/s

0…5V DC

11,500

112

0.05V/s

0…10V DC

11,000

108

0.10V/s

1…5V DC

11,872

116

0.04V/s

0…20 mA

10,500

104

0.20 mA/s

4…20 mA

11,124

108

0.16 mA/s

(1) Limited to 32,764 by programming software.

Ramp Rates for Output Type/Range and Data Formats

Output Data Format

Output Type/Range

Total Counts in Full Scale Number of Counts for

Every 1% of Ramp Rate

Real Units/Second for
Every 1% of Ramp Rate

TIP

N

Not all controllers support alternate output states and this
function. Refer to your controller’s user manual for details.