Rockwell Automation 1769-IF4FXOF2F Compact Combination Fast Analog I/O Module User Manual

Page 57

Advertising
background image

Publication 1769-UM019A-EN-P - October 2008

57

Module Data, Status, and Channel Configuration Chapter 3

Valid Output Data Word Formats/Ranges

This table shows the valid formats and minimum/maximum data
ranges provided by the module.

Valid Output Data

Normal
Operating
Output Range

Full Range

(1)

Raw/
Proportional
Data

Engineering
Units

(2)

Scaled-for-PID

Percent Range

(3)

Full Range

Full Range

Normal
Operating
Range

Full Range

Normal
Operating
Range

Full Range

-10…10V DC

-10.5…10.5V

-32,764…
32,764

-10,500…10,500

0…16,380

-408…16,792

-10,000…
10,000

-10,500…10,500

0…5V DC

-0.5…5.25V

-500…5,248

-1638…17,200

0…10,000

-1000…10,500

0…10V DC

-0.5…10.5V

-500…10,500

-820…17,200

-500…10,624

1…5V DC

0.5…5.25V

500…5,248

-2048…17,404

-1250…10,624

0…20 mA

0…21 mA

0…21,000

0…17,200

0…10,500

4…20 mA

3.2…21 mA

3,200… 21,000

-820…17,404

-500…10,624

(1) Includes amounts over and under normal operating range.
(2) 1 count = 0.001V or 0.001 mA.
(3) 1 count = 0.01%.

Advertising