Module Data, Status, and Channel Configuration Chapter 3
Valid Output Data Word Formats/Ranges
This table shows the valid formats and minimum/maximum data
ranges provided by the module.
Valid Output Data
Normal
Operating
Output Range
Full Range
(1)
Raw/
Proportional
Data
Engineering
Units
(2)
Scaled-for-PID
Percent Range
(3)
Full Range
Full Range
Normal
Operating
Range
Full Range
Normal
Operating
Range
Full Range
-10…10V DC
-10.5…10.5V
-32,764…
32,764
-10,500…10,500
0…16,380
-408…16,792
-10,000…
10,000
-10,500…10,500
0…5V DC
-0.5…5.25V
-500…5,248
-1638…17,200
0…10,000
-1000…10,500
0…10V DC
-0.5…10.5V
-500…10,500
-820…17,200
-500…10,624
1…5V DC
0.5…5.25V
500…5,248
-2048…17,404
-1250…10,624
0…20 mA
0…21 mA
0…21,000
0…17,200
0…10,500
4…20 mA
3.2…21 mA
3,200… 21,000
-820…17,404
-500…10,624
(1) Includes amounts over and under normal operating range.
(2) 1 count = 0.001V or 0.001 mA.
(3) 1 count = 0.01%.