Chapter 3 Module Data, Status, and Channel Configuration

Enable Ramping (ER)

If the selection is enabled (ER = 1), the module controls the ramp rate
of the output when the system transitions from Run to Fault mode
based on the value entered in the channel’s ramp-rate configuration
word. If the selection is disabled (ER = 0), no ramping control of the
output is provided. The default setting is disabled.

Ramp Rate

The ramp rate is defined in terms of the selected range/format in units
per second. For example, in the 0…20 mA range and percent full
scale format, a ramp rate of 1050 is 10% per second (2 mA/s), since
1050 is 10% of the total number of counts in the full scale of the
0…20 mA range when using percent full scale format.

This table describes how the ramp rate is determined for all output
types/ranges and output data formats.

TIP

N

Not all controllers support alternate output states and this
function. Refer to your controller’s user manual for details.

Ramp Rates for Output Type/Range and Data Formats

Output Data Format

Output Type/Range

Total Counts in Full Scale Number of Counts for

Every 1% of Ramp Rate

Real Units/Second for
Every 1% of Ramp Rate

Proportional Counts

-10…10V DC

65,334

(1)

652

0.20V/s

0…5V DC

0.05V/s

0…10V DC

0.10V/s

1…5V DC

0.04V/s

0…20 mA

0.20 mA/s

4…20 mA

0.16 mA/s

Engineering Units

-10…10V DC

21,000

208

0.20V/s

0…5V DC

5,748

56

0.05V/s

0…10V DC

11,000

108

0.10V/s

1…5V DC

4,748

48

0.04V/s

0…20 mA

21,000

208

0.20 mA/s

4…20 mA

17,800

176

0.16 mA/s

Scaled for PID

-10…10V DC

17,203

172

0.20V/s

0…5V DC

18,840

188

0.05V/s

0…10V DC

18,021

180

0.10V/s

1…5V DC

19,452

195

0.04V/s

0…20 mA

17,200

172

0.20 mA/s

4…20 mA

18,224

180

0.16 mA