Wire size and terminal screw torque – Rockwell Automation 1769-IF4FXOF2F Compact Combination Fast Analog I/O Module User Manual
Page 26

26
Publication 1769-UM019A-EN-P - October 2008
Chapter 2 Installation and Wiring
3. Route the wire under the terminal pressure plate.
You can use the bare wire or a spade lug. The terminals accept a
6.35 mm (0.25 in.) spade lug.
4. Tighten the terminal screw making sure the pressure plate
secures the wire.
Recommended torque when tightening terminal screws is
0.68 N•m (6 lb•in).
Wire Size and Terminal Screw Torque
Each terminal accepts up to two wires.
TIP
The terminal screws are non-captive. Therefore, it is possible to
use a ring lug (maximum 1/4 in. o.d. with a 0.139 in. minimum
i.d. (M3.5)) with the module.
TIP
If you need to remove the finger-safe cover, insert a screwdriver
into one of the square, wiring holes and gently pry the cover off.
If you wire the terminal block with the finger-safe cover
removed, you will not be able to put it back on the terminal
block because the wires will be in the way.
Wire Type
Wire Size
Terminal Screw Torque
Retaining Screw Torque
Solid
Cu-90 °C (194 °F)
0.325…2.080 mm
2
(22…14 AWG)
0.68 N•m (6 lb•in)
0.46 N•m (4.1 lb•in)
Stranded
Cu-90 °C (194 °F)
0.325…1.310 mm
2
(22…16 AWG)
0.68 N
•
m (6 lb•in)