MicroLogix 1400 Programmable Controllers 11

Publication 1766-IN001C-EN-P - October 2009

Hazardous Location Considerations

This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or non-hazardous
locations only. The following WARNING statement applies to use in hazardous locations.

Use only the following communication cables in Class I, Division 2 hazardous locations.

WARNING

EXPLOSION HAZARD

• Substitution of components may impair suitability for Class I, Division 2.
• Do not replace components or disconnect equipment unless power has been switched

off.

• Do not connect or disconnect components unless power has been switched off.
• This product must be installed in an enclosure. All cables connected to the product

must remain in the enclosure or be protected by conduit or other means.

• All wiring must comply with N.E.C. article 501-10(b) and/or in accordance with

Section 18-1J2 of the Canadian Electrical Code, and in accordance with the authority
having jurisdiction.

Environment Classification

Communication Cables

Class I, Division 2 Hazardous Environment

1761-CBL-AC00 Series C or later

1761-CBL-AM00 Series C or later

1761-CBL-AP00 Series C or later

1761-CBL-PM02 Series C or later

1761-CBL-HM02 Series C or later

2707-NC9 Series C or later

1763-NC01 Series A or later

1747-CP3 Series