Rockwell Automation 1766-L32xxx MicroLogix 1400 Programmable Controllers Installation Instructions User Manual

Page 33

Advertising
background image

MicroLogix 1400 Programmable Controllers 33

Publication 1766-IN001C-EN-P - October 2009

Working Voltage for 1766-L32BWA, 1766-L32BWAA

Description

Recommendation

Power supply input to
backplane isolation

Verified by one of the following dielectric tests:1836V AC for 1 second or
2596V DC for 1 second

265V AC Working Voltage (IEC Class 2 reinforced insulation)

Input group to backplane
isolation and input group to
input group isolation

Verified by one of the following dielectric tests: 1100V AC for 1 second or
1697V DC for 1 second

75V DC Working Voltage (IEC Class 2 reinforced insulation)

Output group to backplane
Isolation

Verified by one of the following dielectric tests: 1836V AC for 1 second or
2596V DC for 1 second

265V AC Working Voltage (IEC Class 2 reinforced insulation).

Output group to output
group isolation

Verified by one of the following dielectric tests: 1836V AC for 1 second or
2596V DC for 1 second

265V AC Working Voltage (basic insulation) 150V Working Voltage (IEC Class 2
reinforced insulation)

Working Voltage for 1766-L16BXB, 1766-L16BXBA

Description

Recommendation

Input group to backplane
isolation and input group to
input group isolation

Verified by one of the following dielectric tests: 1100V AC for 1 second or
1697V DC for 1 second

75V DC Working Voltage (IEC Class 2 reinforced insulation)

FET output group to
backplane isolation

Verified by one of the following dielectric tests: 1100V AC for 1 second or
1697V DC for 1 second

75V DC Working Voltage (IEC Class 2 reinforced insulation)

Relay output group to
backplane isolation

Verified by one of the following dielectric tests: 1836V AC for 1 second or
2596V DC for 1 second

265V AC Working Voltage (IEC Class 2 reinforced insulation)

Relay output group to relay
output group and FET output
group isolation

Verified by one of the following dielectric tests: 1836V AC for 1 second or
2596V DC for 1 second

265V AC Working Voltage (basic insulation), 150V Working Voltage
(IEC Class 2 reinforced insulation)

Advertising