34 MicroLogix 1400 Programmable Controllers

Publication 1766-IN001C-EN-P - October 2009

Environmental Specifications

Description

1766-L32AWA
1766-L32AWAA

1766-L32BWA
1766-L32BWAA

1766-L32BXB
1766-L32BXBA

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20… 60 °C (-4…140 °F)

Temperature, storage

IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):
-40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% non-condensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):
3 g @ 10… 500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g

Shock, nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
Panel mount - 50 g
DIN mount - 40 g

Emissions

CISPR 11
Group 1, Class A

ESD immunity

IEC 61000-4-2:
4 kV contact discharges
8 kV air discharges

Radiated RF immunity

IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…1000 MHz
3 V/m with 1 kHz sine-wave 80% AM from 1.4…2.0 GHz
1 V/m with 1 kHz sine-wave 80% AM from 2.0…2.7 GHz

EFT/B immunity

IEC 61000-4-4:
±2 kV @ 5 kHz on power ports
±2 kV @ 5 kHz on signal ports
±1 kV @ 5 kHz on communications ports