North american hazardous location approval – Rockwell Automation 1766-L32xxx MicroLogix 1400 Programmable Controllers Installation Instructions User Manual

Page 6

Advertising
background image

6 MicroLogix 1400 Programmable Controllers

Publication 1766-IN001C-EN-P - October 2009

North American Hazardous Location Approval

The following modules are North American Hazardous Location approved: 1766-L32AWA,
1766-L32AWAA, 1766-L32BWA, 1766-L32BWAA, 1766-L32BXB, 1766-L32BXBA

The following information applies when

operating this equipment in hazardous

locations:

Informations sur l’utilisation de cet

équipement en environnements

dangereux:

Products marked "CL I, DIV 2, GP A, B, C, D" are
suitable for use in Class I Division 2 Groups A, B, C,
D, Hazardous Locations and nonhazardous locations
only. Each product is supplied with markings on the
rating nameplate indicating the hazardous location
temperature code. When combining products within
a system, the most adverse temperature code
(lowest "T" number) may be used to help determine
the overall temperature code of the system.
Combinations of equipment in your system are
subject to investigation by the local Authority Having
Jurisdiction at the time of installation.

Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne
conviennent qu’à une utilisation en environnements
de Classe I Division 2 Groupes A, B, C, D dangereux et
non dangereux. Chaque produit est livré avec des
marquages sur sa plaque d’identification qui
indiquent le code de température pour les
environnements dangereux. Lorsque plusieurs
produits sont combinés dans un système, le code de
température le plus défavorable (code de température
le plus faible) peut être utilisé pour déterminer le code
de température global du système. Les combinaisons
d’équipements dans le système sont sujettes à
inspection par les autorités locales qualifiées au
moment de l’installation.

WARNING

EXPLOSION HAZARD

•Do not disconnect while the

circuit is live or unless the area
is known to be free of ignitible
concentrations.

•Do not disconnect connections

to this equipment unless power
has been removed or the area is
known to be nonhazardous.
Secure any external connections
that mate to this equipment by
using screws, sliding latches,
threaded connectors, or other
means provided with this
product.

•Substitution of components may

impair suitability for Class I,
Division 2.

•Do not remove or replace lamps,

fuses or plug-in modules (as
applicable) unless power has
been disconnected or the area is
known to be free of ignitible
concentrations of flammable
gases or vapors.

AVERTISSEMENT

RISQUE D’EXPLOSION

•Couper le courant ou s’assurer

que l’environnement est classé
non dangereux avant de
débrancher l'équipement.

•Couper le courant ou s'assurer

que l’environnement est classé
non dangereux avant de
débrancher les connecteurs. Fixer
tous les connecteurs externes
reliés à cet équipement à l'aide
de vis, loquets coulissants,
connecteurs filetés ou autres
moyens fournis avec ce produit.

•La substitution de composants

peut rendre cet équipement
inadapté à une utilisation en
environnement de Classe I,
Division 2.

•S’assurer que l’environnement

est classé non dangereux avant
de changer les piles.

Advertising